Emptying sewage from the valve-pit sump through service lateral to vacuum main
Type
Journal article
Language
English
Date issued
2022
Faculty
Wydział Inżynierii Środowiska i Inżynierii Mechanicznej
Journal
Environmental Protection Engineering
ISSN
0324-8828
Web address
Volume
48
Number
3
Pages from-to
69-88
Abstract (EN)
A simple hydraulic model of liquid and gas flow from a collecting sump via vacuum service lateral to a vacuum main has been presented. The model was formulated and validated on experimental data and CFD simulations. The standard gas (air) to liquid (sewage) volumetric ratio is roughly equal to the ratio of subsequent admittance times of these two phases, provided that the liquid plug is not fully sucked from the service lateral to the vacuum main during the valve open time. A longer air suction time is needed only when the service lateral is too short to provide enough air to transport the sewage past the nearest downstream lift on the vacuum main. Sizing properly the active sump volume and valve open time for a given service lateral length, one can provide the required air to liquid ratios along the vacuum main, thus minimizing the energy consumption by the vacuum pumps.